Model |
Configuration |
ESS12048E500P4 |
MPPT-SCM 48240R |
INVERTER-HP 12048DR |
BATTERY-LFP 48100R*5 |
Total energy |
240A(60A*4) |
12KW |
500AH(100AH*5) |
25.6kwh |
|
Battery |
Description |
Normal specification |
1 |
Rated Voltage |
51.2V |
2 |
Rated Capacity |
500Ah |
3 |
Rated Energy |
25.6KWH |
4 |
Battery Configuration |
5.12KWH(16S1P) *5PCS |
5 |
Battery Cell |
3.2V100AH 80PCS |
Standard Charge |
1 |
Operation temperature range @charging |
0~45℃ |
2 |
Rated charge voltage |
55.2±0.4V |
3 |
Max charge voltage |
56.8±0.4V |
4 |
Overcharge protection |
58.4±0.4V |
5 |
Allowed MAX charge current(Total) |
275A withstand 30s (every pack 55A) |
6 |
Peak charge current(Total) |
300A withstand 5s (every pack 60A) |
7 |
Rated charge current(Total) |
250A (every pack 50A) |
8 |
Recommend charge current(Total) |
<250A |
Standard discharge |
1 |
Operation temperature range @discharging |
-20~60℃ |
2 |
Output Voltage Range |
40~56Vdc |
3 |
Recommend Working Range |
46~54Vdc |
4 |
Discharge Cut-off voltage |
40V |
5 |
Allowed MAX discharge current(Total) |
550A withstand 30s (every pack 110A) |
6 |
Peak discharge current(Total) |
600A withstand 5s (every pack 120A) |
7 |
Rated discharge current(Total) |
500A (every pack 200A) |
8 |
Recommend discharge current(Total) |
<400A |
Communication |
1 |
RS485 |
For LCD remote |
2 |
CAN |
PC control and monitor |
Inverter (built-in) |
Description |
Normal specification |
1 |
Rated Power |
12KW |
2 |
Output Waveform |
Pure Sine Wave/Same as input (Bypass Mode) |
3 |
Output Voltage |
240Vac(H-H)/120Vac(H-N) ±10% RMS |
4 |
Output Frequency |
50 or 60± 0.3Hz (Inverter mode by sw4 setting) |
5 |
Typical Transfer Time |
4-6ms typical,10ms(Max) |
6 |
THD |
< 3%(Rated voltage full R load) |
7 |
AC Input Range |
184-253Vac (UPS mode) or 140-270Vac (GEN mode) |
8 |
Customized AC Charger |
Battery type selector position 9, special design for LFP, make the battery cycle life Maximization |
9 |
MAX AC Charge Current |
90A |
10 |
Battery priority Function |
Setting by SW5 on position 1 (inverter mode valid), AC automatic come in when battery voltage low alarm at 48Vdc or 50Vdc |
11 |
AC Bypass without charging |
Battery type selector position 0 |
MPPT (built-in) |
Description |
Normal specification |
1 |
PV POWER |
3.0KW*4 |
2 |
PV Input Voltage |
60-145Vdc |
3 |
MPPT Charging Voltage |
56.0Vdc (Fast charging)/54Vdc (Float charging) |
4 |
MPPT Output Current |
60A*4 |
Mechanical Characteristics |
ESS12048E500P4 |
Dimension H*W*D |
Shipping H*W*D |
Weight(N.W.) |
Weight(G.W.) |
1810*560*785mm |
1960*700*870mm |
450KG |
500KG |